| SDN-016-S (RU) |
|
| Input |
|
| Max number of line used(inputs) |
16 |
| Max current on the line |
55mA |
| Typical input voltage |
300 VDC |
| Output |
|
| Max out power |
200 W |
| Max efficiency |
75% |
| Output voltage |
52 V ± 4 V |
| Output voltage |
52 V ± 4 V |
| Earthing |
|
| Earthing connection |
4-pole connector(+ or -, user selectable) |
| |
|
| SDN-016-E (CU) |
|
| Output |
|
| Max. number of lines used for powering (outputs) |
16(tip SDN-16) |
| Max current on the line |
60mA |
| Typical output voltage |
300 VDC |
| Input |
|
| Input voltage range |
from 36VDC to 72VDC |
| Max. input power |
400 W |
| Max. efficency (SDN- 16E) |
75% |
| Earthing |
|
| Earthing connection |
+ pole grounded |
| |
|
| SDN-016 system |
|
| Standards |
|
| Safety |
EN60950, EN60950-21 |
| EMC |
EN55022 class B, ETSI EN 300386 |
| Operating temperature range |
|
Min./max. ambient temperature at relative
humidity 0%- 95%, without condensation |
-20°C to 50°C |
| Dimensions |
|
| Height |
44 mm(1HU) |
| Width |
482 mm(19'') |
| Depth |
167 m |
| Management and control |
|
| Ethernet |
RJ-45 |
| RS485 |
RJ-11, galvanic isolated interface,
with additional galvanic isolated
power supply for power feeding of
extern sensor units,(8-12 VDC, 2mA
(internally limited), 1W, 1500 VDC
insulation voltage. |
| Digital inputs(2) |
Max. Voltage 80V, max. Control
current 2mA (internally limited),
galvanic isolated |
| Digital outputs(2) |
300VDC, max. current 100mA,
galvanic isolated |
| |
|
| Management system(option) |
|
| Ethernet interface |
Ethernet 10Mbps, HTTP, SNMP v1. |
| Communication interface 2(option) |
RJ-485, RJ-11 |
Information/commands available
over HTTP and SNMP |
Number of powering copper pairs
available, Number of powering
copper pairs in operation,
Values of input/output currents
and Number of powering copper pairs
available, Number of powering copper
pairs in operation, Values of
input/output currents and voltages,
Temperature inside of the unit,
Status of digital input pins,
Control of digital output pins. |
| Optional features |
With additional control modules,
which communicate via RS 485 is
possible to supervise additional
parameters like: Room temperature,
Water outflow etc. |